电力104规约报文
发布网友
发布时间:2022-04-21 01:29
我来回答
共3个回答
热心网友
时间:2022-06-17 02:48
是不是测试软件的问题,有可能因为数据太多来不及接收,可以更换测试软件看看,使用支持规约自定义的测试软件测试。
热心网友
时间:2022-06-17 02:49
这个报文是没有问题的,三个字节一个十六进制数据共50个
68 fd fe 10 06 00 09(归一化) d0(连续50个数据)
14 00(响应总召) 01 00 (公共地址01)a1 07 00(开始地址1953) 00 00 00(数据1) 00 00 00 (数据2)00 00 00() 00 00 00 00 00 00 92 0d
00(数据6值3474) 8c 0d 00(3468) 86 0d (3462)00 00 00 00 00 00 00 f1 d8 00 00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00 0e 00 fc 0d 00 0b 0e 00 00 00 00 97 00 00 55 00
00 fe 00 00 0b 01 00 0c 01 00 0e 01 00 01 00 00 9a 0d 00 92 0d 00 8f 0d
00 00 00 00 de 00 00 4d 00 00 0f 01 00 4f 01 00 52 01 00 56 01 00 00 00
00 ed 0c 00 e3 0c 00 fb 0c 00 08 ff 00 08 ff 00 45 d8 00 08 ff 00
08 ff 00 08 ff 00 08 ff 00 08 ff 00 94 0d 00 87 0d 00 86 0d 00 00
00 00 5a 00 00 57 00 00 a4 00 00 b6 00 00 b7 00 00 b7 00 00 00 00 00 00
0e 00 fc 0d 00 10 0e 00 00 00 00 00 00 00 f1 d8 00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00 95 0d 00 93 0d 00 8a 0d 00 00 00 00 00 00 00 f1
d8 00 00 00 00 00 00 00 00 00 00
热心网友
时间:2022-06-17 02:49
这是用我们采购的ET-2000规约分析仪解释出来的测试结果,你看看符合你的需要吗?